PRIOELEC ESL90
Free-Standing Electrical Cabinets

Single and two-door design

Suitable for fire-resistant separation of electrical distributors in escape routes

Description

PRIORIT free-standing electrical cabinets in single- and double-leaf design, suitable for a smoke-tight and fire-resistant separation of electrical distributors in escape and rescue routes (fire load insulation). The housing is made of non-combustible building material class A2 – s1 d0. As standard, cabinets are equipped with a ventilation system in the rear wall, top and bottom cable entry. The inside dimensions are based on the standard distribution panels and mounting plates.

Ventilationprinzip

Function

  • Fire resistance of 90 min, fire resistant
  • Suitable for maintenance of performance for 90 minutes
  • Smoke protection, cold-smoke-proof
  • Empty housing tested and certified by the VDE testing institute according to DIN EN 62208
  • Protection class: IK10, IP 44
  • Protection class II
  • CE marking

Construction

  • Empty housing with high mechanical resistance
  • Door hinges made from stainless steel
  • Door can be unhinged to reduce weight
  • Door hinge can be changed on site
  • Door integrated into body, opening angle approx. 180°
  • 2-point door lock via pivot lever with double-bit cylinder (can be replaced with home locking system)
  • Circumferential fire protection seal, foams automatically in case of fire
  • Cable feed top + bottom for bundle insertion
  • Cable cooling duct on top
  • Fixing rails for installation of device support brackets or mounting plate
  • Tilt safe-guard for housing through fixing lugs at top
  • Integrated base, can be driven under, with removal front panel

Housing accessible from all sides and with removable front panel

Material

Material characteristic

  • Non-combustible board with surface coating, classification A2 – s1, d0
  • Standard CPL surface
  • Colour light grey, similar to RAL 7035, edges and bevels in different colour

Dimension drawing

Effective internal depth

Scope of delivery

  • Empty enclosure, with integrated thermal fuse

Assembly details

File name
PDFDOC
Catalogue excerpt .pdf
Text for tender PRIOELEC ESL90 .pdf.doc
Assembly instructions .pdf
Assembly instructions for built-in fan unit 24 V DC .pdf
Assembly instructions for built-in fan unit 230 V AC .pdf
  • Standardised colours – white, similar to RAL 9016; decor brushed aluminium; primer foil
  • Special decors / special colours
  • Additional rear panel for free housing installation
  • Ventilation system, consisting of fan and smoke detector, ready for connection (230 V AC)
  • Ventilation system, consisting of fan and smoke detector, ready for connection (24 V DC)

Notice

If the fan unit is retrofitted, the usable height is reduced by one height unit.