Fire-resistant cable and pipe bulk head
Self-closing door(s)
Fire-resistant cable and pipe bulk head
Self-closing door(s)

PRIOROOM FEI

Functional Unit, individual

Fire-resistant and individual functional unit

Functional unit is smoke-proof

For the housing of electrical safety systems

  • Construction materials/elements and/or types with national building control test certificate (abP) or national technical approval (NTA). Production of the products is monitored by the building control authority.
  • Tested according to the harmonised European standard
  • Tested according to German standard
  • PRIORIT standard decorative surfaces are resistant to all common household cleaners
  • PRIORIT construction products have standardized locking systems
  • PRIORIT Produkte sind geeignet zur Herstellung einer Feuerwiderstandsfähigkeit von 90 Minuten
  • PRIORIT components and composites, including surfaces, have been tested and classified according to EN 13501-1: non-combustible building material the class A2 – s1, d0
  • PRIORIT construction products have a elastic smoke seal and a fire protection seal that automatically expands in the event of a fire

Description

Fire-resistant and individual functional unit for the housing of electrical safety systems required by the building ordinance. The individually designable functional unit consist of prefabricated non-flammable single components of 42 mm in thickness including the wall, ceiling, fire protection closure („System42“), bulkheads and ventilation elements.
The functional unit is smoke-proof, offers 90 minutes of fire-resistance, and can be constructed in a quick and neat design.
The proof of functional integrity must be documented for ≤ 15 m³ volume capacity in accordance with MLAR 5.2.2 c). It must be ensured that the function of the electrotechnical components in the event of fire is guaranteed for the necessary duration of the function maintenance.

Self-closing door(s)

Function

  • Fire resistance 90 minutes
  • T 90-RS classification of door
  • Door are smoke-tight, tested for continuous operation

Construction

  • Functional unit with high mechanical resistance
  • Fire protection through the formation of a separate fire compartment
  • Door closes flush with body, opening angle ca. 180°, self-closing
  • Door can be unhinged, handle set in aluminium-silver
  • Locking through triple latch lock with single cylinder
  • Door with circumferential smoke and fire seals that automatically expand in the event of a fire
  • Fire-resistant, smoke-proof supply and exhaust air system, each NW 100 mm, for connection to a fire-resistant fire-protection duct system (ventilation system) provided at the site

Ventilation flap

Material characteristic PRIODEK H

Material characteristic

  • Building material with surface coating, classified A2 – s1, d0 non-combustible
  • Standard CPL surface
  • Colour light grey, similar to RAL 7035, edges and bevels in different colour

Dimension drawing

anwendungsbeispiel prioroom fei einfluegelig ansicht

PRIOROOM FEI, single-leaf design

anwendungsbeispiel prioroom fei einfluegelig

PRIOROOM FEI, single-leaf design

anwendungsbeispiel prioroom fei zweifluegelig ansicht

PRIOROOM FEI, two-leaf design

anwendungsbeispiel prioroom fei zweifluegelig

PRIOROOM FEI, two-leaf design

Dateiname
PDF
DOC
Catalouge excerpt PRIOROOM FEI
.pdf
Texts for tenders PRIOROOM FEI
.pdf
.doc
  • Different PRIORIT surfaces possible
  • BEK EI90S shut-off DN 100 triggered by thermal detectors, ready for installation for SYSTEM42 constructions, with a connecting sleeve on one side for DN 100
  • Cable and pipe bulkhead d = 135 mm
  • Cable bulkhead 444 x 204 x 200 mm; PRIODEK H frame
  • Cable bulkhead 444 x 204 x 200 mm; PRIODEK H frame