PRIOELEC EHL91
Electro Hanging Cabinet

Single-leaf version

Fire-resistant separation of electrical distributors in escape routes

Description

PRIORIT electro hanging cabinet in single-leaf design, suitable for a smoke-tight and fire-resistant separation of electrical distributors in escape and rescue routes (fire load insulation). The housing is made of non-combustible building material class A2 – s1 d0. As standard, cabinets are equipped with a ventilation system in the rear wall, top and bottom cable entry. The inside dimensions are based on the electro-technical standard distribution panels and mounting plates.

Function

  • Fire resistance of 90 min, fire-resistant
  • Suitable for fire load insulation of 90 minutes
  • Smoke protection, cold-smoke-proof
  • Protection class: IK10, IP 44
  • Protection class II
  • CE marking

Construction

  • Empty housing featuring high mechanical resistance
  • Door hinges made from stainless steel
  • Door can be unhinged
  • Door stop changeable on site, DIN right/left
  • Door integrated into body, opening angle approx. 180°
  • 2-point door lock via pivot lever with double-bit cylinder (can be replaced with home locking system)
  • Circumferential fire protection seal, foams automatically in case of fire
  • Cable feed top + bottom for bundle insertion
  • Cable cooling duct, top or bottom mounting
  • Additional cable cooling duct, optional
  • Fixing rails for installation of device support brackets or mounting plate

Ventilationprinzip PRIOELEC EHL90

Material

Material characteristic

  • Non-combustible board with surface coating, classification A2 – s1, d0
  • Standard CPL surface
  • Colour light grey, similar to RAL 7035, edges and bevels in different colour

Dimension drawing

Effective internal depth

Scope of delivery

  • Empty enclosure, with integrated thermal fuse

Assembly details

File name
PDFDOC
Catalogue excerpt .pdf
Text for tender PRIOELEC EHL91.pdf.doc
Assembly instructions .pdf
Assembly instructions for built-in fan unit 24 V DC .pdf
Assembly instructions for built-in fan unit 230 V AC .pdf
  • Standardised colours – white, similar to RAL 9016; decor brushed aluminium; primer foil
  • Special decors / special colours
  • Additional cable cooling duct 300 mm high
  • Ventilation system, consisting of fan and smoke detector, ready for connection (230 V AC)
  • Ventilation system, consisting of fan and smoke detector, ready for connection (24 V DC)

Notice