PRIOELEC EW
Electro Wall Recessing Cabinet

Flush mounting with plaster edge

Fire-resistant separation of electrical distribution boards in the escape route

Description

PRIORIT electro wall recessing cabinet in single-leaf design, suitable for a smoke-tight and fire-resistant separation of electrical distributors in rescue routes (fire load insulation). The housing is made of non-combustible building material class A2 – s1, d0. As a standard the cabinets have top and bottom cable entries. The inside dimensions are based on the standard distribution panels and mounting plates.

Function

  • Fire resistance of 30 min, fire-retardant
  • Classification: suitable for fire load insulation of 30 minutes
  • Smoke protection

Construction

  • Empty case for wall recessing
  • Door can be unhinged
  • Door hinge right, may be changed on site to the left
  • Door closes flush with body, opening angle ca. 180°
  • 2-point door locking with swing lever and double-bit cylinder
  • Circumferential fire seals automatically expand in the event of a fire
  • Cable entries top + bottom
  • Attachment points for electric installations

Material

Material characteristic

  • Non-combustible board with surface coating, classification A2 – s1, d0
  • Standard CPL surface
  • Colour light grey, similar to RAL 7035, edges and bevels in different colour

Dimension drawing

Effective internal depth

Assembly details

File namePDFDOC
Catalogue excerpt .pdf

Text for tender PRIOELEC EW 30 Minuten .pdf

.doc

Assembly instruction PRIOELEC EW .pdf
  • EDF fixing cross beam