PRIOROOM
Fire Resistant Storage Room

Fire resistant room

Space-saving alternative due to 42 mm panel thickness

Quick and clean installation

Description

Fire-resistant space of non-combustible A2 – s1, d0 building material for the construction of storage and service areas required by building regulations: theatre/props– sales areas/waste – escape and rescue routes/vending machines and others. With only 42 mm panel thickness, the room offers a space-saving alternative to conventional solid construction. Benefits: chemically highly stable, decorative internal and external surface, fast and clean to install, extensible, can be re-configured. The room is smoke-tight and provides 90 minutes fire resistance.

Function

  • Fire resistance 90 minutes: fire-resistant
  • Wall: EI 90 classification
  • Ceiling: F 90/EI 90 a↔b
  • T 90-RS classification of door(s)
  • Door(s) are smoke-tight, tested for continuous operation

Construction

  • Room with high mechanical resistance
  • Fire protection through the formation of a separate fire compartment
  • Modular design of prefabricated parts
  • Overall height up to 3,670 mm, overall width up to 6,500 mm and unlimited depth
  • Door height and width up to max. 2,500 mm
  • Door(s) with 3D stainless steel bands, opening angle ca. 170°
  • Door(s) with hydraulic door closer, triple locking system, prepared for single cylinder
  • Fire-resistant vents K90 NW 100 mm, freely positionable within the wall elements
  • Fire resistant cable bulkhead 125 mm diameter, 60% assignable, freely positionable within the wall elements
  • Room can be equipped with lighting, ventilation, shelves and fire protection bulkheads

Material

Material characteristic

  • Non-combustible board with surface coating, classification A2 – s1, d0
  • Standard CPL surface
  • Colour light grey, similar to RAL 7035, edges and bevels in different colour

Dimension drawing

File name
PDFDOC
Catalogue excerpt .pdf
Text for tender PRIOROOM .pdf
.doc
  • Cable and pipe bulk head for wall
  • Fire protection glasses for inspection closure and door
  • Ventilation flap
  • Fire damper
  • Single-leaf, double-leaf doors freely positionable
  • Door hold-open device
  • Smoke detector
  • Stainless steel cladding in V2A / V4A